FIRE DAMPER TYPE КПД

The fire damper type КПД for smoke exhausting is intended for use in supply and exhaust systems for smoke ventilation of buildings and structures for various purposes, as well as in systems for removing smoke and gas after a fire from premises protected by gas, aerosol or powder fire extinguishing. The valve is used in accordance with the requirements of Snip 2.04.05.

FIRE DAMPER TYPE КПД

The fire damper type КПД for smoke exhausting is intended for use in supply and exhaust systems for smoke ventilation of buildings and structures for various purposes, as well as in systems for removing smoke and gas after a fire from premises protected by gas, aerosol or powder fire extinguishing. The valve is used in accordance with the requirements of Snip 2.04.05.

The fire valves consist of a body, a swing-type flap damper and a damper opening / closing mechanism. The damper has overhanging length outside the body frame. The fire valve is installed in stair elevators, as well as on branches of air ducts of smoke or air supply ducts. The valves are available in round and rectangular designs. The normal (initial) position of the damper is closed (normally closed). According to their functional purpose, the dampers are used as smoke dampers (Д). The valves can be equipped with two types of an electromagnetic actuator, an electric actuator with a built-in return spring without ТРУ and a reversible “open-closed” electric actuator.
The fire valves have a density loss limit of E60 and E90. The fire valves can be operated at temperatures of the working medium from -30 ° С to +45 ° С. The environment and air must not contain aggressive gases and vapors that destroy materials, paint coatings and electrical insulation of the product. The fire valve must not be installed in rooms of categories A and B for explosion and fire hazard, in ventilation systems and in places where explosive and aggressive media are sucked out, as well as in systems that are not subject to cleaning from combustible sediments. The fire valves are manufactured in climatic versions for operation in areas with moderate У (moderate) and УХЛ (boreal) climates and location categories 3 and 4 according to GOST 15150.

Example of fire damper designation:

КПД- 200×200 ER (E 60), where;

КПД – Fire damper smoke removal;
200 × 200 – standard size AxB, mm;
ER – drive type;
(E 60) – fire resistance limit;

 

DesignFire resistance limitExecution
E 601 часКПД (60)
E 901,5 часаКПД (90)

 

DesignActuator type
ЭElectromagnetic
ЭМReversible electric actuator
ЭРElectromechanical actuator with spring return without ТРУ

 

 

Weight, kg (no more)1502002503004005006007008009001000A
1802302803304305306307308309301030a
15018012,712,813,25
V
a
l
v
e

s
e
c
t
i
o
n

h
e
i
g
h
t

m
m
20023012,813,813,914,916,0
25028013,2513,914,3515,4517,719,75
30033014,915,4516,5518,522,725,7
40043016,017,718,522,524,828,428,731,3
50053019,7522,724,828,531,632,835,738,357,2
60063025,728,431,636,238,941,643,465,2
70073028,732,838,940,644,247,772,3
80083031,335,741,644,250,553,275,2
90093038,343,447,753,257,581,5
1000103057,265,272,375,281,586,5
BbValve section width, mm

 

 

 

DD1D2Lотв.Weight, kg (no more)
200230260300610,67
225255285611,6
250280310613,7
280310340814,5
315345375815,8
355385415817,4
400430460819,2
4504805101022,3
5005305603101024,2
5605906203401228,6
6306606903751233,7
7107407704151240,8